MHTC2A humidity and temperature transmitter module is designed base capacitive humidity and temperature sensor by Ningbo Junrong Electron. This product utilizes humidity sensor capacitor (HS1101, France Humirel) and temperature sensor (LM35, America), with characteristics of stable and wide power supply, excellent anti-jamming, high accuracy and protecting power and it also use craftwork of SMD, so own extremely small body, stable and reliably performance. Each product inspected and 48 hours aging test before sells. The quality guarantee time is 12 months.

 

 

Humidity and temprature transmitter module

 
……………………………………………………………………………………………………………………………

1. Application

   Electron , pharmaceutical industry, food processing, warehouses, tobacco, textile, weather, office building, warm air-conditioning, libraries and museum.

2. Shape

Model         encapsulation                shape             

MHTC2A         with shell              detail to the picture

3. Specification

(1) Power supply (vin )                        DC   10-30V

(2) Electrical current                         6MA (max 8mA)

(3) Temperature operating range                0 ~ 80

(4) Humidity operating range                   0 ~ 100%RH (dew point)

(5) Humidity measuring range                   2 ~ 99%RH

(6) Temperature storing range                  -20 ~ 85

(7) Humidity storing range              under 95%RH (no dew point)

(8) Humidity measuring Accuracy   MHTC2A-I    ±4%RH ( at 25, 60%RH )

                                  MHTC2A-H    ±3%RH ( at 25, 60%RH )

(9) Typical humidity data responding to output

 

Based on the power supplied by 12.0V and the environment at 25℃

Humidity (%RH)

0

10

20

30

40

50

60

70

80

90

100

Voltage (V)

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

                       Resistance under 5Ω

(10) Temperature testing feature        ±1 (LM35 integrated temperature sensor)

(11) Temperature dependence(reference)    ±2%RH (12.00V DC, 0–100%RH, at 25, 0-50)

(12) Voltage dependence (reference)

4. Testing condition

  At atmosphere 25, power supply 12.0V

Putthehumiture sensor module in dry air at 25℃/20%RH environment 5 minutes before testing, then put it into testing container keeping the Humidity 60%RH, 5 minutes later, measure the voltage.

 
………………………………………………………………………………………………………………………………………………………………………………………………………
                   
           
                 
     

Ningbo Jiangbei Junrong Electron Technology Co.,Ltd

TEL:86-574-87386939  87386839  87386739 

FAX:EXT 616